    Gas Fire Alarm Panel system is the heart of gas releasing fire detection and alarm systems, It connects many types of detection components, alarm components, and activation components, and has very powerful input and output functions.

    enquiry
    • Specifications
    • Product Features
    • Application Scenario
    • More Information

    A gas fire alarm panel system is an automatic gas release panel that is used to control the start and stop of a fire suppression system and to input or output signals to the gas release warning sign, manual release station, heat detector, smoke detector, fire alarm bell, sequential starter, etc. It is the central controller of a complete fire extinguishing system, it is the heart of industrial and commercial fire protection systems.

    Many fire suppression systems can be controlled by this extinguishing control panel, such as FM200, Perfluorohexanone, Carbon dioxide, Inert gas, dry chemical powder, foam, and water mist. They are compatible with each other and even universal.

    Like a car engine, choosing a gas fire alarm control panel with stable performance, reliable quality, and sturdy casing is very important, our control panel is made of high-quality components, with high quality and a long lifespan, It has been successfully applied in major alarm detection and fire protection projects both domestically and internationally, Various fire protection companies, consulting companies, engineering companies, installation companies, and construction companies are our main customer groups.

    For example, Bangladesh Telecom has successfully applied our gas fire alarm panel system and ultra-fine dry powder fire extinguishing system to various distribution rooms, transmission rooms, power generation rooms, and computer rooms.

    GAS FIRE ALARM PANEL AWGEC2169:

    • Name and function: gas control panel for fire suppression systems.
    • Type: Conventional style.
    • Model number: AWGEC2169.
    • Size: 350*280*107 mm.
    • Color: The default color is red, and other colors can be customized if needed.
    • Main power supply: 90-240 VAC, 50/60 Hz.
    • Battery: 2*12 Volt, 2.3 Ah sealed lead acid gel, self-regulated.
    • Battery low voltage protection data: 21 Volt.
    • Battery charge voltage: 27.6 VDC nominal.
    • Alarm terminal output current: Maximum 200 mA.
    • EM valve output current: Maximum 1.2 A.
    • Relay contact rating: 1A at 30 VDC.
    • Power supply rating: 3 A.
    • The zone numbers: 2.
    • Maximum detector numbers for each zone: 16 pieces of detectors (except mcps).
    • Material: Carbon Steel metal.
    • Rating of terminal blocks: 12 to 18 AWG (0.75 to 2.5 mm2).
    • high decibel alarm function: Included.
    • Communication protocol: CAN and RS485 2 wires.
    • Wire between the control board and detector: 12 to 18 AWG (0.75 to 2.5 mm2) 2-core shielded cable.
    • Ambient temperature: -5 to +40℃ or 23 to 104℉.
    • Relative humidity: from 5% to 95% RH, non-condensing.

    SMOKE DETECTOR AWCSD381:

    • Name of the components: smoke detector.
    • Model number: AWCSD381
    • Size: 100*100*48mm.
    • Standby current:  less than 120uA at 24 VDC.
    • Maximum alarm current: less than 15mA at 24 VDC.
    • Operating voltage: 9 to 28 VDC no polarity.
    • Smoke alarm sensitivity: 0.1-0.15dB per meter.
    • Application field: for indoor use only.
    • Wiring: the promise of 2 bus systems zone+ and zone-.
    • Product material and color: White ABS.

    HEAT DETECTOR AWCTD382:

    • Component name: heat detector.
    • Item number: AWCTD382.
    • Dimension: 99.8*99.8*48mm.
    • Relay output: 0.5A at 24 VDC.
    • Fix temperature alarm: 57°C ( 135°F ) A2R or 70°C ( 158°F ) A2R.
    • Rise alarm rate: 7.1°C/5S A2R.
    • Connection type: 2 wires.
    • Two LEDs (RED) status: blinks in normal conditions and becomes stationary during the fire.

    STROBE SOUNDER(HORN&STROBE) AWCSS2166-2:

    • Product name: conventional fire strobe sounder.
    • Model: AWCSS2166-2.
    • Size: 154*115*51 mm.
    • Color: Red.
    • Sound type: 3 types.
    • Power supply: 12 to 24 Volt.
    • Operating current: less than 60mA at 24 VDC.
    • Alarm SPL: more than 100dB at 1M.
    • Flash Period: less than 1.0 seconds.
    • IP protection: IP30.

    MANUAL RELEASE STATION AWGD201:

    • Name of the product: manual release station.
    • Item number: AWGD201.
    • Dimension or Size: 100*100*98mm.
    • Color: Silver and Pink.
    • Connector: Dry NO.
    • Power: 3A at 220 Volt.
    • Standard: EN54-2 & EN54-4 &EN12094-1.

    ABORT SWITCH AWGD202:

    • Component name: abort switch.
    • Component number: AWGD202
    • Connector 1: Dry NO (3A @ 220V).
    • Connector 2: Dry NC (3A @ 220V).
    • Color: Silver and Yellow.

    MODE SWITCH AWGD203:

    • Product name: Mode Switch (Optional).
    • Dimension: 110*87*39mm.
    • Input voltage: 18 to 28 VDC.
    • Work current: less than 25 mA.
    • Application: Switch control.
    • Ambient temperature range: -20 to +50℃.

    FIRE ALARM BELL AWCBL2166-A-6:

    • Name of components: fire bell.
    • Usage: Fire sound activated alarm.
    • Dimension: 150*61mm.
    • Bell base: Carbon iron steel.
    • Work current: 25mA @24 VDC.
    • Work voltage: 20 to 28 VDC.
    • Wiring: 2 wires.
    • Volume: more than 68 dB.

    GAS RELEASE WARNING SIGN AWGRS2158:

    • Entry name: Gas release warning sign (gas release indicator light).
    • Model: AWGRS2158.
    • Operating voltage: 24 VDC, non-polarized.
    • Operating current: less than 70mA at 24 VDC.
    • Power supply: 24 VDC non-polarized.
    • Flashing period: 1.2 to 1.5 seconds.

    SEQUENTIAL STARTER AWGD205:

    • Components name: Sequential starter or sequence starter (Optional).
    • Series number: AWGD205.

    For details please read its dedicated page: Modular Sequence Starter for Fire Suppression Systems.

    Gas fire detection and alarm systems

    This product is a gas fire extinguishing controller and its other components are carefully planned and developed by our technical personnel, which has many technical and functional characteristics:

    • Small size, light weight, easy to install on walls.
    • When releasing gas, the delay time can be reset between 0 to 60 seconds, so it is resetable.
    • There are two backup batteries, which are built-in when the AC power is turned off.
    • AC power and backup power (2 batteries) can be freely and automatically switched.
    • The product has anti misoperation function, and when the abort switch is pressed, the fire extinguishing system will not have any spraying action.
    • Equipped with GSM module functionality (Optional).
    • The outer shell is made of metal, which is very sturdy and durable, and has visible glass windows that can be opened and closed.
    • Resetable 24VDC port, capable of connecting 4-wire fire suppression devices.
    • Equipped with pre-alarm function, is able to issue alerts in a timely manner.
    • High compatibility and coordination between various components.
    • According to European standards EN54-2, EN54-4, EN12094-1.

    This type of controller is required for any defense area where a fire extinguishing system is installed.

    We know that the application range of fire extinguishing systems is very wide, so the application range of this controller is also in the same industry, we list some classic installation scenarios as follows:

    • Computer rooms.
    • Data processing rooms.
    • Super-market and shops.
    • Power generator room.
    • Underground pipe gallery.
    • Museums and library.
    • Various factories and warehouses.
    • Battery energy storage container.
    • Communication base stations.

    Its application range is too broad for us to list all of them.

    When a general engineering project requires the installation of a fire extinguishing system, it is also necessary to install an alarm system, including this gas fire alarm panel.

    So when our company is designing fire protection projects, we will work together to design alarm systems and fire extinguishing systems for customers, Because this is a complete fire protection project and also convenient for the owner to inspect and accept.

    If you have any questions about the alarm or fire extinguishing system, please contact us promptly, and our professional designers will provide you with the perfect answer.

    Enquiry Form ( we will get back you as soon as possible )

    Name:
    *
    Email:
    *
    Message:

    Verification:
    5 + 7 = ?

    Maybe you like also