The aerosol fire extinguishing device is a highly concentrated fire extinguisher, The fire extinguishing agent inside has been made into a brown mud-like shape, making the size of this product smaller.
Its other components, such as ceramic particles, wire mesh, insulation rings, starters, usw., have also been condensed into small shapes, so this product can be installed in the vast majority of narrow spaces.
Am wichtigsten, its fire extinguishing efficiency is very high, and the designed concentration reaches 100 Gramm pro Kubikmeter.
Aerosol extinguishers can be installed in small spaces, and then of course can also be installed in ATMs.
Below are some basic index values and characteristics of thermo bulb type aerosol generator:
- Artikelnummer: 250ST
- Dimension and Tolerance: Φ12,6*14,4 Zentimeter (±01 mm).
- Actuating Mode: glass bulb actuation.
- Optional Rated Temperature: 57℃, 68℃, 79℃, 93℃.
- Weight of Extinguishing Agent Powder: 250 Gramm.
- Löschmittelqualität: 0.25 kg.
- Produktgewicht: 2600 Gramm.
- Produktkonzentration: 100 Gramm pro Kubikmeter.
- Cover-Bereich: wenigstens 2.5 Kubikmeter.
- Feuerunterdrückungsmodus: Totalüberflutung oder lokale Anwendung.
- Entladezeit: 10 Sekunden.
- Device Startup Delay Time: 1 Zweite.
- Main Materials: Strontiumsalz, Kaliumsalz, 304 rostfreier Stahl, Bitte beachten Sie unsere Sicherheitsdatenblatt.
- Lebenszeit: mehr als 10 years according to the result of the aging test.
- Fire Suppression Types: Bewertung A, B, C, E.
- Production Time: 7 Days.
- Lead Time: ungefähr eine Woche bis zwei Wochen.
- Verpackung: Carton Box and Polyfoam.
Notiz: The aerosol fire extinguisher installed on the ATM can also have other automatic starting methods, so wie die THERMAL WIRE CORD.
Für mehr Details, please contact customer service.
The smart Condensed Fire Extinguishing generator is a clean agent fire suppression system.
Compared with the FM200 fire suppression system and Novec 1230 System, the aerosol suppression system has the following advantages:
- It works without a pipe network.
- It does not need a pressurized cylinder.
- It does not have a pressure gauge.
- It can be applied in a small space.
That is why it can be installed in the narrow space in the ATMS.