PREFACE

Dispositivo de extinção de incêndio com pó seco ultrafino em armazéns elevados

Three-dimensional high-value warehouse is now a major form of warehousing, A vantagem deste tipo de armazém é que ocupa uma pequena área e tem uma grande capacidade de armazenamento.

It is a form of logistics that realizes computer-controlled automatic access and is now widely used in the storage of lubricating oils, óleos hidráulicos, paints, and other chemical products as well as raw materials such as acetone and other substances.

Na China, three-dimensional high-bay warehouse fire fighting systems, mainly are water spray systems, water sprinkler systems, ultra-fine dry powder systems, etc.

Ultra-fine dry powder fire extinguishing system is suitable for three-dimensional elevated warehouses because of its pipe-less network and installation and maintenance is easy. Assim sendo, it is designed to be used in warehouses for tobacco, papel, paint, and communication equipment.

This paper briefly analyses the spraying principle of the ultra-fine dry powder fire extinguishing device, fire extinguishing efficiency, and design and application, to give the choice of fire protection facilities in the high-bay warehouse as a reference.

SELECTION OF FIRE EXTINGUISHING DEVICES

Product Definition and Classification

Ultrafine dry powder fire extinguishing devices according to the extinguishing agent delivery mode points, are pipe network fire extinguishing systems and non-pipe network fire extinguishing systems, this article focuses on analyzing non-pipe network types.

Suspended dry powder is a type of ductless system that can be applied to overhead storage rooms, it is also divided into two types: pressurized storage and non-pressurized storage.

Pressurized storage fire extinguishing device refers to the storage of pressure gas and fire extinguishing agent in the same container, which is a device that uses pressure gas to push the extinguishing agent to extinguish a fire. This type of fire extinguishing device has good dispersal performance, alta eficiência de extinção de incêndio, and high safety of use, and is widely used in various places.

Non pressurized storage fire extinguishing device refers to a device in which the gas stored in the fire extinguishing agent storage container is in a normal atmospheric pressure state, and when used, high-pressure gas is generated by the combustion of the gas in the fire extinguishing agent storage container, which drives the spraying of the fire extinguishing agent. Non-pressure storage fire extinguishing devices are divided into spherical-shaped, barrel-shaped, basin-shaped, and bowl-shaped according to their appearance.

Product Comparison and Selection

From experimental and practical applications, the spraying performance, safety performance, and fire extinguishing performance of the spherical ultrafine dry powder fire extinguishing device are the best.

Spherical ultrafine dry powder fire extinguishers can be applied to three-dimensional warehouses, garagens, e oficinas de fábrica; And the basin-shaped and bowl-shaped ultrafine dry powder fire extinguishing devices, due to their relatively small volume, can be applied to car engine compartments, armários de distribuição, and other applications.

Due to the significant impact force of non-pressure storage ultra-fine dry powder fire extinguishing devices during spraying, And accompanied by a loud noise exceeding 90 decibels, it is easy to damage the ceiling of the three-dimensional elevated warehouse and pose a threat to personnel safety.

Em suma, when selecting fire extinguishing devices for three-dimensional elevated warehouses, we should try to use pressurized storage fire extinguishing devices as much as possible, If you want to use non-pressurized storage fire extinguishing devices, you should choose spherical ones.

extintores de pó químico seco para armazém

SELECTION OF FIRE EXTINGUISHING AGENTS

Ultra-fine dry powder fire extinguishing agent, the smaller the particle size, the higher the fire extinguishing performance. Atualmente, there are two main types of ABC ultrafine dry powder fire extinguishing agents used in the market:

  • fosfato de amônio.
  • ultrafine dry powder fire extinguishing agent.

Ammonium Phosphate

For this type, its main extinguishing mechanism is to block the combustion chain reaction, which is the chemical inhibition effect. 90% of the particle size of this fire extinguishing agent is below 20UM, Its fire extinguishing efficiency is ≤0.120/m3, qual é 4 vezes a do agente extintor de pó seco comum.

Ultrafine ABC Dry Chemical Powder Fire Extinguishing Agent

For this type, 90% of the particle size of the fire extinguishing agent is below 15UM, This type of fire extinguishing agent organically combines the advantages of chemical fire extinguishing with the advantages of physical fire extinguishing through a composite method. The chemical suppression effect on flame burning, o efeito de sufocamento na combustão sem chama, e o efeito de isolamento e resfriamento da radiação térmica são as manifestações concentradas desse tipo de agente extintor de incêndio.

Better OptionUltrafine ABC Dry Chemical Powder

Ao extinguir um incêndio em material sólido, as partículas de material compósito do agente extintor formam uma película vítrea na superfície do sólido em chamas em altas temperaturas, isolando o material de combustão do ar e extinguindo instantaneamente a combustão sem chama do sólido. A eficácia deste tipo de agente extintor de incêndio é ≤ 0,065kg/m3, que é mais do que 10 vezes maior que os agentes extintores de pó seco ABC comuns.

Devido ao denso empilhamento de mercadorias em armazéns elevados, quando ocorre um incêndio, o fogo se espalha rapidamente; To quickly extinguish the fire and reduce the losses caused by the fire, people should choose fire extinguishing agents with high fire extinguishing efficiency. Ao mesmo tempo, it can effectively reduce the number of fire extinguishing devices hanging on elevated shelves and reduce the damage caused by elevated shelves.

Dispositivo de supressão de incêndio de pó químico seco ABC na sala de armazenamento

DESIGN OF FIRE EXTINGUISHING SYSTEM

There are generally three ways to design a dry powder fire extinguishing system:

  • Total flooding fire extinguishing application.
  • Local protection fire extinguishing application.

Design of Total Flooding Fire Extinguishing Application

The total flooding application fire extinguishing system refers to the specified time to spray a certain concentration of ultrafine dry chemical fire extinguishing agent into the protective area. and make it an evenly filled fire extinguishing system for the entire protective zone.

The elevated warehouse is high and has a large volume, the height of this warehouse is usually 8 para 28 metros, volume exceeding 20000 metros cúbicos; It is difficult to achieve the same level of extinguishing concentration as the extinguishing agent sprayed in such a tall space within the specified extinguishing time.

Ao mesmo tempo, the logistics method of automated warehouse access cannot separate the warehouse into the required space for total flooding.

Assim sendo, it is not appropriate to use the total flooding application of the fire extinguishing system for elevated warehouses.

Design of Local Protection Fire Extinguishing Application

The local protection application fire extinguishing system is a fire extinguishing system that directly sprays dry powder extinguishing agents toward the protected object or areas considered dangerous.

Article 3.3.1 of GB50347Code for Design of Dry Powder Fire Extinguishing Systemsstipulates thatthe design of local application fire extinguishing systems can use either the area method or the volume method.

When the fire location of the protected object is a plane, the area method should be used; when the area method cannot completely cover all surfaces, the volume method should be used”.

UMA. Area Method Design

According to the standard, since the protection area of the nozzle (ou bico) of the fire extinguishing device is determined by the vertical direction of the protected surface, the calculation of the protection area also needs to take the area of the vertical projection of the overall protection surface.

When multiple fire extinguishing devices are used, the edges of their projected areas should overlap each other to ensure that the projected area can fully cover the protected object and leave no gaps in its coverage.

The area method applies to fire extinguishing systems for Class B (liquid) fires and other flat-protected objects. Because the goods in the dense shelves in the elevated warehouse, and even the entire dense shelves, are three-dimensional, not only the top plane of the goods needs to be protected, but also the four sides and bottom, and these goods are multi-level and dense, which cannot be covered by the vertical projection area.

Assim sendo, we cannot use the area method for the design of fire suppression systems in elevated warehouses.

B. Volume Method Design

Devido à necessidade de extinguir o fogo plano no topo das mercadorias nas estantes densas do armazém elevado, bem como os fogos nos quatro lados e na parte inferior, o método do volume deve ser usado no projeto do sistema de extinção de incêndio.

De acordo com padrões nacionais e estrangeiros relevantes, o volume do objeto protegido deve ser calculado usando o volume assumido da tampa fechada, com a parte inferior da tampa incluída sendo a parte inferior real. Quando não há nenhuma estrutura de vedação real nas laterais e na parte superior da cobertura fechada, A distância deles até a borda externa do objeto protegido não deve ser inferior a 1.5 metros.

The area method and volume method are two different design methods for local protection fire extinguishing systems. The area method design applies to designs that protect objects that are flat, such as surface protection for limited flammable liquids. The volumetric design method applies to designs that protect objects that are polyhedral, such as goods that exhibit three-dimensional properties items, shelves, etc. The two methods apply different protection objects, such as the designed dosage of extinguishing agent and extinguishing. The requirements for the arrangement of fire devices also vary.

C. Area Method Design VS Volume Method Design

If the area method is used for the design of the ultra-fine dry powder fire extinguishing system in an elevated warehouse, it will inevitably result in a serious shortage of the designed amount of fire extinguishing agent and the number of fire extinguishing devices, which will not meet the requirements of the fire extinguishing concentration and prevent the fire that should have been extinguished from being extinguished.

When arranging the fire extinguishing devices, it will also prevent the protection of several surfaces other than the vertical plane, and prevent these fires from being extinguished.

We should use the volume method to design the dry powder fire extinguishing systems in elevated warehouses. Only in this way can we ensure that in the event of a fire, the extinguishing agent sprayed will extinguish the fire in all directions, playing a role in protecting personal and property safety.

sistemas de extinção de incêndio com pó químico seco ABC sem vazamentos 21

CONCLUSÃO

Em suma, o armazém elevado tem um amplo espaço. Devido à densa colocação de objetos e outras características, ao selecionar dispositivos de extinção de incêndio com pó seco ultrafino para instalações de proteção contra incêndio, é aconselhável escolher dispositivos de extinção de incêndio com bom desempenho de pulverização.

O agente extintor preenchido no dispositivo de extinção de incêndio deve usar agentes extintores de pó seco ultrafino com alta eficiência de extinção de incêndio.

We should use the volumetric method to design fire-extinguishing devices