  • namn: Conventional Fire Alarm Control Panel AW(Aware)-CFP-2166.
  • Modellnummer: AW-CFP-2166.

Fire Alarm Control Panel Data Sheet

Below the datasheet are the main parameters of this product, you can see more information about it from there:

  • Modellnummer: AW-CFP-2166-01/32.
  • Main Supply Voltage: 110 VAC or 240 VAC.
  • Internal Power Supply: 27.2 VDC.
  • Total Output Current Limited: 500mA @ 240 VAC (3A @ 240 VAC).
  • Main Supply Monitor for Fault: Ja.
  • Battery Protection for Low Voltage: Ja.
  • Batteries (Default Configuration): 12V2AH*2.
  • Number of Circuits: 1 till 32.
  • Line Fault Monitor for Open Circuit: Ja.
  • Line Fault Monitor for Short Circuit: Ja.
  • Line Fault Monitor for Detector Removal: Ja, if the end-of-line monitor unit is fitted in place of the line resistor.
  • End-of-Line Device: 6.8, 5% tolerance, 0.25W(color code-blue, Grey, röd, gold).
  • Detector Continuity Diodes: Silicon IN 4001(required if end-of-line monitor unit fitted to give detector removal fault).
  • Call Point Resistor Value: 470 to 680Ω, 0.225 eller 0.5 watts.
  • Maximum Number of Heat Detectors or Smoke Detectors Per Zone: 20 (based on a total detector current of 2mA, each detector consuming 100μA).
  • Maximum number of belts @20mA of each sounder output: 20.
  • Maximum number of manual call points per zone: No Limits.
  • Number of general circuits: 2.
  • Battery Fuse: 1.5A F 20mm.
  • Sounder Outputs: 50mA F 20mm.
  • Output Type: NC and NO Relay.
  • Maximum Current: 100 mA.
  • Dimensions: 272*200*70 mm, 320*231*90 mm, 395*502*124 mm, 362*565*124mm.
  • Net weight (without battery): 4.0 till 8.0 kilogram.
  • Gross weight (without battery): 5.8 till 12.5 kilogram.

Role of the Conventional Fire Controller

A fire alarm control panel is equivalent to a central processing unit, commanding the working status of accessories such as smoke sensors, temperature sensors, startknappar, and alarm bells.

As long as you have a fire extinguishing controller, you have the heart of a fire extinguishing system.

Conventional Fire Alarm Control Panel

The main features of this product are listed below:

  • AW-CFP2166 series of conventional fire alarm panels are designed based on EN54 part 2&4 standards.
  • It is a modular design, the panel can extend from 1 zone to 32 zones easily.
  • It has 2 2-level control mode with a lock.
  • It has 24VDC and 5VDC power supply output.
  • It has "FIRE" och "FAULT" signal output.
  • It has 2 general sounders output.
  • Each/every zone has 1 circuit detector input.
  • Easy zone can be disabled by a button.
  • It has a "RESET" button to reset the panel.
  • It has a "SIRENCE" button to stop BUZZER and SOUNDERS.
  • It has an "EVACUATE" button to start a manual fire alarm immediately.
  • It has a battery low protection function, when the battery voltage is lower than 21VDC, the battery will be cut off automatically until the mains power is on.
  • It has an optional GSM module for fire alarm by SMS.
  • It is economical, miljövänlig, and easy to maintain.
  • The office.
  • The bank.
  • Insurance company.
  • Höghus.
  • The school.
  • The university.
  • The supermarket.
  • The shopping mall.
  • The commercial and residential buildings.
  • The power distribution room.
  • The computer room.
  • The generator room.
  • The wind turbine.
  • Solar energy.
  • The mining.
  • transportation Fields.
  • The marine.
  • The workshops and warehouse.
  • The archives, bibliotek, museer,
  • The government facilities.

This conventional fire control panel could be used for gaseous fire suppression systems, skum, ABC dry chemical and aerosol fire extinguishing systems, etc.

Before project acceptance, the technician should do system debugging first.