Gör allt för säkerhets skull,för en säker värld!

Profile of IG541 Gas Fire Suppression System

» Vår blogg » Profile of IG541 Gas Fire Suppression System

Profile of IG541 Gas Fire Suppression System

November 25, 2017

IG541 gas fire suppression system is a mixed gas fire extinguishing system, be made up of a storage cylinder and hoods, container valve, high-pressure hose, backventil, manifold relief valve, säkerhetsventil, pressure redistrict, munstycke, driving gas cylinder, Pneumatic actuator, start-up pipeline, it is an intelligent fire suppression system.
According to different application areas, it is divided into a single system and a combined distribution system, its fire extinguishing method is total flooding, and it can cover a single protection zone and muti-protection zone.
It has advanced technology, is perfect for fire suppression, and is easy to maintain.

It is with 3 different activation methods:

  • a. Automatic
  • b. Manual
  • c. Mechanical

IG541 fire extinguishing agent is made up of N2, Ar, and CO2 gas and combined, their mixing ratio is N2 for 52%, Ar for 40%, and CO2 for 8%; it is a purely natural gas fire extinguishing system and is now the most environmentally friendly gas fire suppression system.

ANSÖKAN

IG5541 gaseous fire suppression system is mainly for bellowing fire:

  • A. Solid Surface Fire, Fire Class A.
  • B. Liquid Fire, Fire Class B.
  • C. Gas Fire, Fire Class C.
  • D. Electrical Fire, Fire Class E.
    It mainly applies to the following:
    Datorrum, Telekommunikationsrum, kontrollrum, library, museum, arkiv, data storage room, elgeneratorrum, oil-immersed transformer room, substation room, circuit breaker, recycle units, hydraulic device, drying equipment, deducting equipment, painting room and so on.

THE MAIN PARAMETERS OF THE IG541 Gas Fire Suppression System

Product Model Number QMH15/70,QMH15/80,QMH15/90
Agent Cylinder Volume 70L, 80L, 90L
Extinguishing Agent Storage Pressure 15 Mpa (2 degrees centigrade)
Max Working Pressure 17.2 Mpa
Agent Refilling Density 0.2115 kilograms per liter
Actuator Power 24 voltage
Extinguishing Style Total Flooding
Släckningstid Mindre än 60 sekunder.
Actuation Methods Automatic, Manual, and Mechanical
Driving Gas Nitrogen Gas
Driving Gas Refilling Pressure 6 Mpa (20 degrees centigrade)
Arbetstemperatur 0 till 50 degrees centigrade

ATTENTION

  • 1. Handle with care, don’t collide and upside down.
  • 2. Don’t put fire extinguishing agent cylinders and driving gas cylinders near heat, and don’t expose them to the sun; transportation and storage temperatures require 0 till 50 degrees centigrade, and keep dry and ventilation.
  • 3. irrelevant personnel please do not touch the equipment in case of any accidents.
  • 4. The device commissioning staff should be familiar with the basic structure, working principle, performance and operating procedure, and even every part’s basic structure and working status.
  • 5. When doing remote Maintenance, please do as per operating procedure, in case of any miss-operation.
  • 6. In the protection zone there should be no combustible and conducting dust and corrosion parts, the device can not be able to get shock or collision, in case of any please make protection for the equipment.
  • 7. Before discharging, all people in the protection zone should leave within the delay time (0-30 seconds adjustable), and after discharging, don’t enter until waste gas is expelled.
  • 8. For Other safety measures please obey some relative guarantees and policies.
fire extinguishing systems inert gas

FÖRFRÅGAN:

    Se mer av brandsläckningsprodukter

    Kanske gillar du också